Cable Loss Measurement
This tutorial covers measuring coaxial cable characteristics using the NanoVNA-H, including loss per unit length, electrical length, and velocity factor.
What You Will Learn
Section titled “What You Will Learn”- Measuring cable loss using S11 and S21 methods
- Determining cable electrical length
- Calculating velocity factor
- Using Time Domain Reflectometry (TDR) mode
- Finding cable faults
Cable Parameters
Section titled “Cable Parameters”| Parameter | Description | Typical Values |
|---|---|---|
| Loss (dB/m) | Signal attenuation per meter | 0.01 - 1 dB/m (frequency dependent) |
| Velocity Factor (VF) | Speed of signal vs. light | 0.66 - 0.85 |
| Impedance | Characteristic impedance | 50 or 75 ohms |
| Electrical length | Length in wavelengths | Varies with frequency |
Method 1: S21 Transmission Loss
Section titled “Method 1: S21 Transmission Loss”The most direct method - measure signal loss from one end to the other.
-
Set frequency range
Cover the frequencies you care about:
- HF work: 1 MHz - 30 MHz
- VHF/UHF: 50 MHz - 500 MHz
-
Calibrate with THRU
Connect your Port 1 cable directly to Port 2 cable (without the cable under test).
Perform THRU calibration: CAL > CALIBRATE > THRU > DONE
-
Connect the cable under test
- Port 1 to one end of the cable
- Port 2 to the other end
-
Read the loss
The S21 trace shows transmission loss in dB.
At each frequency, the loss (in dB) equals the cable’s total loss at that frequency.
-
Calculate loss per unit length
Loss/meter = Total loss (dB) / Cable length (m)
Example: 3.5 dB loss for a 25m cable = 0.14 dB/m
Method 2: S11 Return Loss with Short
Section titled “Method 2: S11 Return Loss with Short”Use reflection measurement when you only have access to one end of the cable.
-
Short the far end
Place a short circuit at the far end of the cable. You can:
- Use a commercial short standard
- Touch inner and outer conductors together
- Solder a wire across the connector
-
Calibrate Port 1
Perform OPEN, SHORT, LOAD calibration at Port 1.
-
Connect the cable
Connect the near end of the cable to Port 1.
-
Read S11
The signal travels down the cable, reflects from the short, and returns.
One-way loss = |S11 in dB| / 2
Example: S11 = -2.4 dB means one-way loss = 1.2 dB
Measuring Electrical Length
Section titled “Measuring Electrical Length”The electrical length determines how the cable transforms impedance.
-
Short the far end
-
Set a narrow frequency span
For a quarter-wave section at 100 MHz:
- CENTER:
100M - SPAN:
50M
- CENTER:
-
Enable S11 phase display
Go to DISPLAY > FORMAT S11 (REFL) > PHASE
-
Find quarter-wave frequency
At odd multiples of quarter-wavelength, the phase crosses through 0 degrees (going from +90 to -90 or vice versa).
-
Calculate electrical length
At frequency F where phase = 0:
- Quarter-wave length at F: lambda/4 = c / (4 * F * VF)
Calculating Velocity Factor
Section titled “Calculating Velocity Factor”Velocity factor tells you how fast signals travel in the cable compared to free space.
-
Measure the physical length
Measure the actual cable length in meters.
-
Find the quarter-wave frequency
Using the method above, find where the shorted cable shows 0-degree phase.
-
Calculate velocity factor
VF = (4 * Physical length * Frequency) / c
Where c = 299,792,458 m/s (speed of light)
Example:
- Physical length: 2.5 m
- Quarter-wave frequency: 24 MHz
- VF = (4 * 2.5 * 24,000,000) / 299,792,458 = 0.80
Common Velocity Factors
Section titled “Common Velocity Factors”| Cable Type | Velocity Factor |
|---|---|
| RG-58, RG-8 (solid PE) | 0.66 |
| RG-213 | 0.66 |
| RG-8X, RG-58 foam | 0.78 |
| LMR-400 | 0.85 |
| Air-dielectric hardline | 0.92 - 0.95 |
| Twin-lead (300 ohm) | 0.82 |
Using the Cable Measurement Mode
Section titled “Using the Cable Measurement Mode”The NanoVNA firmware includes a cable measurement function.
-
Short the far end of the cable
-
Set the velocity factor
Go to MARKER > MEASURE > CABLE (S11)
Or use DISPLAY > TRANSFORM > VELOCITY F.
Enter your cable’s velocity factor (e.g., 66 for 0.66).
-
Read the calculated length
The display shows estimated cable length based on the velocity factor and measured electrical properties.
-
Adjust velocity factor for accuracy
If you know the physical length, adjust VF until the measured length matches.
Time Domain Reflectometry (TDR)
Section titled “Time Domain Reflectometry (TDR)”TDR mode converts frequency-domain data to distance, showing reflections along the cable.
-
Enable TDR mode
Go to DISPLAY > TRANSFORM
Select TRANSFORM ON
-
Choose transform type
- LOW PASS IMPULSE: Shows individual reflections
- LOW PASS STEP: Shows impedance changes
-
Set velocity factor
DISPLAY > TRANSFORM > VELOCITY F.
Enter your cable’s VF as a percentage (66 for 0.66).
-
Set window function
DISPLAY > TRANSFORM > WINDOW
- MINIMUM: Sharp resolution, more ringing
- NORMAL: Balanced
- MAXIMUM: Smooth, reduced resolution
-
Interpret the display
The horizontal axis now shows distance. Peaks indicate reflections:
- Peak at the far end = normal termination
- Peaks in between = faults, connectors, or impedance discontinuities
Finding Cable Faults
Section titled “Finding Cable Faults”TDR signature: Large positive peak
In frequency domain: S11 magnitude stays near 0 dB (all power reflected), phase changes with frequency
Finding the fault:
- Enable TDR mode
- Set correct velocity factor
- Peak location shows distance to break
TDR signature: Large negative peak
In frequency domain: S11 magnitude stays near 0 dB, 180-degree phase shift pattern
Finding the fault:
- Enable TDR mode
- Peak location shows distance to short
- Often caused by water ingress or crushed cable
TDR signature: Smaller peak, possibly with ringing
In frequency domain: S11 varies with frequency, may show periodic pattern
Finding the fault:
- Enable TDR mode
- Look for intermediate peaks (not at the end)
- May indicate water, kinks, or damaged connector
Comparing Cable Loss
Section titled “Comparing Cable Loss”To compare cables or check for degradation:
-
Create a reference measurement
Measure a known-good cable section.
-
Save the reference
Use DISPLAY > TRACE > STORE TRACE to save the reference.
-
Measure the test cable
-
Compare visually
The stored trace appears as a reference line. Differences indicate:
- Higher loss: Possible water ingress, damage, or poor connectors
- Irregular response: Possible intermittent connection
Loss vs. Frequency Table
Section titled “Loss vs. Frequency Table”Measure and record loss at multiple frequencies for complete characterization:
| Frequency | Total Loss (dB) | Loss/100m (dB) |
|---|---|---|
| 3.5 MHz | ||
| 7 MHz | ||
| 14 MHz | ||
| 28 MHz | ||
| 50 MHz | ||
| 144 MHz | ||
| 432 MHz |
Practical Tips
Section titled “Practical Tips”Minimizing measurement error
Section titled “Minimizing measurement error”- Use quality connectors and adapters
- Keep adapter count to minimum
- Calibrate including any necessary adapters
- For long cables, use the S11/short method to avoid extra adapters at the far end
When to be concerned
Section titled “When to be concerned”- Loss significantly higher than manufacturer specification
- Loss that varies with frequency differently than expected
- TDR showing unexpected reflections
- Intermittent results when cable is moved
Next Steps
Section titled “Next Steps”- Your First S11 Measurement - Basic reflection measurements
- Full Calibration - Accurate calibration procedure
- Tuning HF Antennas - Use cable knowledge for antenna work